ships without HTTP credentials configured, intended for an installer to set them on first use. On firmware 2.4.4 and earlier, a unit left in this unconfigured state serves the web management interface without requiring any login. An attacker with network access to such a unit can reach full device controls, including power relay management, device reboot, remote access service configuration, and network settings, which could allow disruption of connected infrastructure or physical damage to equipment.
Analysis and contextual insights are available on OpenCVE Cloud.
Vendor Solution
Tycon Systems has released firmware 2.4.5, which resolves this vulnerability by requiring an administrator username and password to be set before the web interface is served. Further inquiries can be directed to security@tyconsystems.com. Tycon Systems recommends setting an administrative username and strong password on the Network Configuration page and confirming in a private browser window that a login is required, for units still running firmware 2.4.4 or earlier. Repeat this after any factory reset. Tycon Systems recommends not exposing the web interface to the Internet, as it is HTTP only. The unit should be kept on a private network, behind a firewall or VPN.
Tracking
Sign in to view the affected projects.
No advisories yet.
Fri, 04 Sep 2026 22:30:00 +0000
| Type | Values Removed | Values Added |
|---|---|---|
| Weaknesses | CWE-288 | |
| References |
|
Fri, 04 Sep 2026 21:45:00 +0000
| Type | Values Removed | Values Added |
|---|---|---|
| Description | The web management interface of Tycon Systems TPDIN-Monitor-WEB2 does not perform server-side validation of credentials during the login process. By submitting empty values for both credential fields, an unauthenticated remote attacker can bypass the authentication check and establish a valid administrative session. This grants full access to device controls including power relay management, device reboot, remote access service configuration, and network settings, which could allow an attacker to disrupt connected infrastructure or cause physical damage to equipment. | The Tycon Systems TPDIN-Monitor-WEB2 ships without HTTP credentials configured, intended for an installer to set them on first use. On firmware 2.4.4 and earlier, a unit left in this unconfigured state serves the web management interface without requiring any login. An attacker with network access to such a unit can reach full device controls, including power relay management, device reboot, remote access service configuration, and network settings, which could allow disruption of connected infrastructure or physical damage to equipment. |
| Title | Tycon Systems TPDIN-Monitor-WEB2 Authentication Bypass Using an Alternate Path or Channel | Tycon Systems TPDIN-Monitor-WEB2 Missing Authentication for Critical Function |
| Weaknesses | CWE-306 |
Mon, 27 Jul 2026 16:30:00 +0000
| Type | Values Removed | Values Added |
|---|---|---|
| Metrics |
ssvc
|
Mon, 27 Jul 2026 13:15:00 +0000
| Type | Values Removed | Values Added |
|---|---|---|
| First Time appeared |
Tycon Systems
Tycon Systems tpdin-monitor-web2 |
|
| Vendors & Products |
Tycon Systems
Tycon Systems tpdin-monitor-web2 |
Fri, 24 Jul 2026 22:00:00 +0000
| Type | Values Removed | Values Added |
|---|---|---|
| Description | The web management interface of Tycon Systems TPDIN-Monitor-WEB2 does not perform server-side validation of credentials during the login process. By submitting empty values for both credential fields, an unauthenticated remote attacker can bypass the authentication check and establish a valid administrative session. This grants full access to device controls including power relay management, device reboot, remote access service configuration, and network settings, which could allow an attacker to disrupt connected infrastructure or cause physical damage to equipment. | |
| Title | Tycon Systems TPDIN-Monitor-WEB2 Authentication Bypass Using an Alternate Path or Channel | |
| Weaknesses | CWE-288 | |
| References |
| |
| Metrics |
cvssV3_1
|
Status: PUBLISHED
Assigner: icscert
Published:
Updated: 2026-09-04T21:28:52.355Z
Reserved: 2026-07-13T18:17:10.040Z
Link: CVE-2026-61884
Updated: 2026-07-27T14:32:57.239Z
Status : Deferred
Published: 2026-07-24T22:16:50.963
Modified: 2026-09-04T22:17:17.723
Link: CVE-2026-61884
No data.